This project was to replace multiple Medium Voltage XLP 15kv Cables that were originally installed in between 1970 and the 1990s at 7 locations and provide additional new equipment such as PST Cabinets. All primary electrical distribution system voltages were 12.47kv Delta and were all constructed with 3 conductors plus a bare ground copper conductor. All new enclosures provided and installed were Stainless Steel and suitable for coastal environments. New lengths at multiple locations ran from 160 LF to 1400 LF and were all AWG single conductor per phase, 220 MILS EPR 15 kV MV105 133% insulation copper core with tape shield. All Electrical Man Hole locations were left with a service loop and all Fire Taped. All Medium Voltage Terminations with the new and resourced equipment were replaced or installed. A tensiometer was used and tracked during all cable pulls. All new cable terminations to transformers, PST’s and switches utilized Boot terminations.